Model FP01101MCB02A. Toshiba Industrial Lithium-ion Battery SCiB™ Industrial Pack has features such as compact and lightweight, rapid charging, long life, and higher safety compared to conventional lead-acid battery. It is conducive to improvement of operation and cost reduction in production facilities or logistic warehouses.
Specifications
| Item | Value | Unit | Conditions | Source |
|---|---|---|---|---|
| Rated capacity | 22 | Ah | table 0, row 'Rated capacity' table 0, row '定格容量' SCiB_toshiba_en.pdf p.4, table 3, row 'Rated capacity', column 'SCiB™ Industrial Pack (48V)' | |
| Nominal voltage | 50.6 | V | table 0, row 'Nominal voltage' table 0, row '公称電圧' SCiB_toshiba_en.pdf p.4, table 3, row 'Nominal voltage', column 'SCiB™ Industrial Pack (48V)' | |
| Voltage range | V | table 0, row 'Voltage range' table 0, row '使用電圧範囲' SCiB_toshiba_en.pdf p.4, table 3, row 'Voltage range', column 'SCiB™ Industrial Pack (48V)' | ||
| Nominal energy | 1113 | Wh | table 0, row 'Nominal energy' table 0, row '電力量' SCiB_toshiba_en.pdf p.4, table 3, row 'Nominal energy', column 'SCiB™ Industrial Pack (48V)' | |
| Dimensions (W×D×H) | 247×188×165 | mm | table 0, row 'Dimensions' table 0, row '寸法' SCiB_toshiba_en.pdf p.4, table 3, row 'Dimensions', column 'SCiB™ Industrial Pack (48V)' | |
| Weight | 16 | kg | table 0, row 'Weight' table 0, row '質量' SCiB_toshiba_en.pdf p.4, table 3, row 'Weight', column 'SCiB™ Industrial Pack (48V)' | |
| Module configuration | 2 in series | table 0, row 'Module configuration' table 0, row 'モジュール構成' | ||
| Ambient temperature (operating) | CEL | table 0, row 'Ambient temperature for use' table 0, row '使用周囲温度' SCiB_toshiba_en.pdf p.4, table 3, row 'Ambient temperature', column 'SCiB™ Industrial Pack (48V)' | ||
| Ambient temperature (storage) | CEL | 35°C or less is recommended | table 0, row 'Ambient temperature for storage' table 0, row '保管周囲温度' | |
| Ambient humidity | %RH | without dew condensation | table 0, row 'Humidity for use / storage' table 0, row '使用 / 保存湿度' SCiB_toshiba_en.pdf p.4, table 3, row 'Ambient humidity', column 'SCiB™ Industrial Pack (48V)' | |
| Maximum allowable current | 125 | A | 200 seconds | table 0, row 'Maximum allowable current' table 0, row '最大許容電流' SCiB_toshiba_en.pdf p.4, table 3, row 'Max.charge/discharge current', column 'SCiB™ Industrial Pack (48V)' |
| Charging method | CCCV | constant current / constant voltage | table 0, row 'Charging method' table 0, row '充電方式' | |
| Charge voltage (CV) | 57.2 | V | CV set point | table 0, row 'Charging method' table 0, row '充電方式' |
| Rapid charge | charging completes within 1 hour; 20 minutes with a customised charger | SCiB_toshiba_SIP_en.pdf p.3 | ||
| Cycle life | 20000 | cycles | more than 80% of capacity remaining, SOC 50-90% cycles (23Ah cell; the pack uses 23Ah cells) | SCiB_toshiba_SIP_en.pdf p.3 |
| Discharge capacity at low temperature | % | at -30°C ambient, relative to C/3 discharge capacity at 25°C | SCiB_toshiba_SIP_en.pdf p.3 | |
| Usable depth of discharge | 100 | % | lead-acid batteries are commonly used at about 50% DOD | SCiB_toshiba_SIP_en.pdf p.3 |
| Ingress protection | IP53 or equivalent | table 0, row 'Dust-proof Water-proof' table 0, row '防塵防水' | ||
| Protection functions | Over charge protection, Over discharge protection, High temperature protection, Low temperature protection | table 0, row 'Protection function' | ||
| Main circuit terminal | Bolt/Nut (M6), to be prepared by the customer | SCiB_toshiba_SIP_en.pdf p.7 | ||
| Interface connectors | IN harness JST 8-pin (pack side 08R-JWPF-VSLE-D), DO harness JST 6-pin (06R-JWPF-VSLE-D), OUT harness JST 8-pin (08T-JWPF-VSLE-D); CAN 2.0B at 250 kbps | SCiB_toshiba_SIP_en.pdf p.7 | ||
| Digital outputs | FET output up to 30 V / 20 mA: 2-point SOC in four steps, 3-point warning (low voltage, overvoltage, high temperature), 1-point DC 5 V source up to 25 mA | SCiB_toshiba_SIP_en.pdf p.7 | ||
| Remarks | Using two units of [*2] in series | SCiB_toshiba_en.pdf p.4, table 3, row 'Remarks', column 'SCiB™ Industrial Pack (48V)' | ||
| Weight relative to lead-acid | about a quarter of an equivalent lead-acid battery | SCiB_toshiba_SIP_en.pdf p.6 |